How it works
These gateways expose the controls of a compatible Daikin indoor unit to a BACnet system. The Daikin-side connection and the building network are separate choices. Check both before selecting a gateway.
Choosing a product
For a VRV or Sky Air unit using P1/P2, start with DK-RC-BAC-1. For a residential indoor unit with S21, identify whether the building controller requires BACnet/IP or MS/TP. The 1L version is MS/TP only.
Applications and formats
- P1/P2 to BACnet
- DK-RC-BAC-1 / INBACDAI001R000 supports BACnet/IP or MS/TP for a compatible commercial indoor unit.
- S21 to BACnet MS/TP
- DK-AC-BAC-1L / INBACDAI001I100 is the serial-network version for a compatible residential indoor unit.
- S21 to BACnet/IP or MS/TP
- DK-AC-BAC-1 / INBACDAI001I000 supports either network. This model is discontinued. Ask ASG to confirm the quantity available.